Power Lynx Mini
|
|
Uninterruptable Power system Single Phase (350-2000 W)
|
|
|
|
The Power Lynx is always on-line, eliminating noise, spikes, surges and brownouts. When the utility fails, the Power Lynx inverter will continue to provide AC voltage without the slightest interruption.
The Power Lynx's inverter generates an output sine wave that uses a high frequency PWM. The output voltages available are 208Y/120 or 480Y/277 (consult the factory for others). The output Transformer isolates your critical load from the any source of noise. The inverter uses an output transformer in the Power Lynx that will always protect your equipment.
Our monitoring is very comprehensive. Each output voltage is monitored for voltage, current and KVA levels. Even if the output voltages are 120 and 277, each output is monitored independently so you always know what is going on with your critical loads. The input is monitored adjustable via the |
 |
front panel. The microprocessor will store any alarm so a history is always available. The RS 232 and RS 485 ports will allow for remote monitoring.
The Power Lynx's battery charger is temperature compensated for maximum battery life. We use sealed maintenance free batteries (other batteries are available, please check with the factory), the microprocessor is settable to exercise the batteries on a regulator bases, and so the battery is never a question. An automatic battery equalize is also provided. The equalize operation is settable, so the battery can be equalized according to the battery manufacturer guidelines for your application.
|
|
|
|
 |
|
 |
UL 1778
|
 |
High Efficiency >92% |
 |
Reliability (200,000 hrs.) |
 |
Energy Star Rated - TP1 |
 |
Industrial Application |
 |
Service Access Front Only |
 |
DSP/PWM Inverter |
 |
Proven Non-linear load Capability |
|
|

 |
Maintenance Bypass Switch |
 |
Outdoor or Harsh Environment Enclosure |
 |
Phoenix "Hydrogen Off- Gassing Termination" |
 |
Output Circuit Breakers |
 |
Normally - Off Output Circuit Breakers |
 |
Seismic Rated Bracket
|
 |
Remote Panel
|
*Specifications are subject to change without notice.

|
|
|

|
 |
|


| *Power Rating |
350, 525, 700, 875, 1050, 1400 and 2000W |
| *Input Voltage |
120, 208, 240, or 277 VAC |
| *Input Voltage Reg. Range |
+10%, -15% |
| *Output Voltage |
120 or 277 VAC |
| *Output Voltage Regulation |
±2% typical |
| *Output Frequency Range |
60 Hz ±5% |
| *Output Wave Form |
Sine-wave <5% @ 100% linear load |
| *Crest Factor |
2.5:1 Typical |
| *Input Protection |
Input Main Circuit Breaker |
| *Output Protection |
Output Main Circuit Breaker |
| *Surge Protection |
The unit will protect itself and the load against surges as defined in ANSI/IEEE C62.45 category A and B. |
| *Output Transformer |
Shield, isolation transformer |
| *Isolation |
Inverter complete from line |
| *Battery |
Sealed maintenance-free (AGM) lead acid |
| *Recharge Current |
10 times discharge |
| *External battery |
Provision for hardwire connection of external battery cabinets or DC source. |
| *Efficiency |
>92% |
| *Audible Noise |
<45 dB measured on Response Curve "A" |
| *Safety Agencies |
UL 1778 |
| *Operating Temperature |
0 to 40C (32 to 104F.) |
| *Storage Temperature |
-20 to 60C (-4 to 140F.) |
| *Humidity |
5 - 95% Non-condensing |
* Consult factory for others, Specifications are subject to change without notice.
|
|
Mini
Series |
Power
Rating
|
UPS
|
Weight
|
Battery
Type |
Voltage
(VAC) |
Output
CB's
|
Output
wave Form
|
| Dimentions |
Sealed
Mainte
nance
Free
(AGM)
Lead
Acid |
Input |
Output |
Quantity 1, 3 or 6 |
Sinewave
<5% THD with 100% Linear Load |
|
Mini
|
VA/KW |
W |
H |
D
|
(LBS)
|
Select
120
208
240
or
277
|
Select
120/
240
or
277
|
| 500/350 |
24" |
25"
|
16"
|
125 |
| 750/500 |
24" |
25" |
16"
|
150 |
| 1000/700 |
24" |
25" |
16"
|
200 |
| 1250/875 |
24" |
25" |
16"
|
225 |
| 1500/1050 |
24" |
25" |
16"
|
250 |
| 2000/1400 |
24" |
25" |
16"
|
275 |
| 3000/2000 |
24" |
25" |
16"
|
300 |
|

|
|
|
|